Influence of Parameters on Airside Performance of Wavy Fin-and-tube Heat Exchangers with Hydrophilic Coating under Dehumidifying Conditions

Zhang Yuanming,Ding Guoliang,Ma Xiaokui
DOI: https://doi.org/10.3969/j.issn.0253-4339.2007.02.003
2007-01-01
Abstract:The effects of space of fins,number of tube rows and relative humidity of incoming air on airside performance of wavy fin with hydrophilic coating under dehumidifying conditions were experimentally explored for seven wavy fin-and-tube heat exchangers with hydrophilic coating.The Colburn factor and the Fanning friction were applied to describe airside heat transfer and friction characteristics,respectively.The test results indicate that the Colburn factor and the friction factor increase with the decrease of space of fins.The Colburn factor decreases when number of tube rows increases while the effect of number of tube rows on the friction factor is small.When inlet relative humidity increases,the Colburn factor increases and the friction factor almost remains unchanged.Inlet relative humidity has a more significant effect on the Colburn factor when the inlet water temperature is lower.
What problem does this paper attempt to address?