Accuracy Self-Adaptive Method of Fin and Tube Heat Exchanger Simulation Software

RUI Yin-bo,DING Guo-liang,WU Zhi-gang
DOI: https://doi.org/10.3321/j.issn:1006-2467.2006.08.022
2006-01-01
Abstract:A method to correct the simulation accuracy of the fin-and-tube heat exchanger model was presented,which can choose correction strategies automatically according to the number of the experiment data points the users can offer.When the number of data points is small,the air side heat transfer coefficient is corrected with polynomial regress.When the number of data points is large,the air side heat transfer coefficient is corrected with artificial neural network.The practical simulation with this method shows: ① the max and mean deviation of heat flow rate are 28.96% and 11.12% respectively,when no correction is made;② the max and mean deviation of heat flow rate are 15.33% and 5.38% respectively,with polynomial correction method;③ the max and mean deviation of heat flow rate are 4.9% and 1.0% respectively,when artificial neural network correction is used.
What problem does this paper attempt to address?