Research Three Simulation Models for Fin and Tube Exchanger Used by Air Handle Unit

Feng QIU,Bo GU,Wei BAI
DOI: https://doi.org/10.3969/j.issn.1005-0329.2010.07.015
2010-01-01
Abstract:Iumped parameter model,distributed parameter model and sub-row-parameter model for fin and tube exchanger were designed,which simulate the heat transfer performance.Develop the reasonable iterative algorithm for three models above to calculate quickly and stable in the system.Compared with experiment data,the errors of lumped parameter and distributed parameter are more than sub-row-parameter,with 19%,12%,4.6%.Because sub-row-parameter considers the influence of rows,which matches the actual physical model.Meanwhile,for the lumped parameter model,analyze why the heat transfer quality is always more than the experiment,and give advice to the user.
What problem does this paper attempt to address?