Analysis of Two Sets of Substation DC Busbars of Which Cathode and Anode Are Mixed to Connect

LI Xiu-jin,WANG Nai-ke,DENG Jie-qing,YUAN Yu-bo,SUN Tian-yu
DOI: https://doi.org/10.3969/j.issn.1009-0665.2011.03.011
2011-01-01
Abstract:The normal operation of DC system is of great significance to the safety and stability of substation.Through actual cases,the phenomenon of two set of DC busbars of which cathode and anode are mixed to connect is introduced.And the equivalent circuit model is built and analyzed,which is simplified by the basic circuit principle.The reasons for grounding alarm caused by two sets of DC busbars of which cathode and anode are mixed to connect are illustrated.In addition,the damage of two sets of DC busbars of which cathode and anode are mixed is also analyzed,and effective methods to search the electric mixed point are also proposed.
What problem does this paper attempt to address?