Estimation of the minimum shielding failure flashover current for first and subsequent lightning strokes to overhead transmission lines

Zacharias G. Datsios,Pantelis N. Mikropoulos,Thomas E. Tsovilis
DOI: https://doi.org/10.1016/j.epsr.2014.03.008
IF: 3.818
2014-08-01
Electric Power Systems Research
Abstract:ATP-EMTP simulations are performed to estimate the minimum shielding failure current causing flashover in overhead transmission lines with operating voltage in the range of 66kV up to 735kV. This critical current, affecting shielding failure flashover rate, is of great importance for assessing the insulation coordination of overhead transmission lines and the connected substations. The minimum shielding failure current causing flashover of line insulation is highly dependent upon insulator string flashover modelling and, also, markedly higher than that calculated according to the relevant IEEE Std 1243-1997 simplified expression. A modification of the latter is suggested by using multiplication factors of 1.5 and 1.65 for first and subsequent lightning strokes, respectively, so as to account for the increased dielectric strength of line insulator strings under non-standard lightning overvoltage surges. Alternatively, the critical currents can be respectively estimated by using average negative breakdown gradients per unit length of insulator string of 680kV/m and 750kV/m. The shielding failure flashover rate of the overhead transmission lines, being greatly influenced by insulator string flashover modelling, is lower than that obtained based on the critical current according to IEEE Std 1243-1997.
engineering, electrical & electronic