The impact of electrode dielectric coating on the insulation integrity of GIS/GITL with metallic particle contaminants

S. Zhang,M.M. Morcos,H. Anis,S.M. Gubanski,K.D. Srivastava
DOI: https://doi.org/10.1109/61.997890
IF: 4.825
2002-04-01
IEEE Transactions on Power Delivery
Abstract:Coating the inside surface of gas insulated switchgear (GIS) enclosures with a dielectric film reduces the deleterious effect of electrode surface roughness, impedes the development of metallic particle initiated microdischarges, increases the field required to lift particles, and reduces the charge acquired by particles, all of which help alleviate the adverse effect of contaminating metallic particles on insulation withstand. The performance of particle-contaminated compressed gas systems with dielectric coated electrodes is analyzed. Two mechanisms for the transfer of charge from electrodes to contaminating particles are considered, namely, conduction through the coating layer and microdischarges in the surrounding gas. The paper presents an electrostatic study of the particle lifting fields with dielectric covered electrodes. The overall breakdown strength of the system is evaluated and the results are discussed in the light of experimental findings.
engineering, electrical & electronic
What problem does this paper attempt to address?