Identifying fouling mechanism in a novel hybrid cooling tower's bundles: Application in concentrated solar power (CSP) plant

Afaf Zaza,El Ghali Bennouna,Alfredo Iranzo,Youness El Hammami
DOI: https://doi.org/10.1016/j.icheatmasstransfer.2023.107139
IF: 6.782
2023-12-01
International Communications in Heat and Mass Transfer
Abstract:In this paper, structural, chemical, and thermos-physical characteristics of fouling and tube materials for hybrid cooling tower bundles in Concentrated Solar Power (CSP) facilities are addressed. Toward an in-depth understanding and a comparison of the fouling mechanism on galvanized steel and polymer tubes, results obtained from the characterization studies and the experimental test correlations were used to calculate the sticking probability (P) and deposit bond strength (ξ) based on the Kern-Seaton model. According to the data, the polymer tube had three times higher the adhering probability of the galvanized steel tube with a value of PPf = 3.15*102 Ns/m2, whereas the deposit bond strength was two times lower with a value of ξPf = 3.49*10−8. The results revealed that when it comes to polymer tubes, the ones with a finer surface structure tend to attract foulants from deluge water more readily. However, once foulants are attached to the heat transfer surface, it's simpler to be removed. The substantial increase in kaolinite and gypsum phases can explain this occurrence. On the other hand, galvanized tubes, exhibit the opposite behavior. It is anticipated that this constructive study will shed light on performance-enhancing fouling mechanisms and offer a scientific basis for thermal engineers.
thermodynamics,mechanics
What problem does this paper attempt to address?