Investigation on fouling of enhanced tubes used in a cooling tower water system based on a long-term test

Chao Shen,Rong Gao,Xinlei Wang,Yang Yao
DOI: https://doi.org/10.1016/j.ijrefrig.2019.05.003
IF: 4.14
2019-08-01
International Journal of Refrigeration
Abstract:<p>In order to investigate the fouling of enhanced tubes, a continuous fouling test on eight enhanced tubes and one plain tube was conducted for 98 days, using a medium fouling potential water as the test water at a water velocity of ∼1.6 m/s. Four periods were defined for fouling development based on the test data in this work: introduction period, initial deposit period, rapid deposit period, and stabilization period. The rank of asymptotic fouling resistance of nine test tubes was as follows: Tubes 9 &gt; 7 &gt;6 &gt; 5 &gt; 1 &gt;3 &gt;4 &gt;2 &gt;8. The pressure drops of the nine tubes increased by 0.1 kPa to 1.32 kPa due to fouling deposit at the end of the fouling test. A fouling resistance prediction model was developed, which had a maximum error of 0.0645 for predicting the fouling resistance ratio.</p>
engineering, mechanical,thermodynamics
What problem does this paper attempt to address?