EXPERIMENTAL RESEARCH ON THE FOULING RESISTENT OF INTERNAL HELICAL-RIB TUBES

李蔚,张巍,李冠球,张政江,秦新安,王铁坤,徐志明
DOI: https://doi.org/10.3321/j.issn:0253-231x.2009.09.041
2009-01-01
Journal of Engineering Thermophysics
Abstract:The experiments on fouling resistant of the seven different helical-rib tubes in cooling tower have been carried by us for a long time.The ranges of geometric parameters were number of rib starts(18~45),helix angle(25~45 deg.),and height(0.33~0.55 mm).The fouling mechanism is a combination of precipitation fouling and particulate fouling.Based on the Prandtle analogy,βfactor (β=(A_w/A_(wp))/(A_c/A_(cp)),A_w is the wetted area,A_c is the cross section area,and the subscript p means the plain tube) was introduced to revise the semi-theoretical fouling model.The geometric parameters were proved to affect the fouling growing strongly.A new unified theoretical fouling correlation has been developed for all the tubes.The new correlation can be directly used to assess the fouling potential of enhanced tubes in actual cooling water situations.
What problem does this paper attempt to address?