Fouling model of internal helical-rib tubes based on prandtle analogy

Wei Zhang,LI Guan-qiu,ZHANG Zheng-jiang,XU Zhi-ming,Wei Li.
2008-01-01
Abstract:The fouling experiments on heat transfer performance of seven copper helically ribbed tubes in cooling tower were taken under the condition of 1.07 m/s water velocity and Reynolds number is 16000. The ranges of geometric parameters were number of rib starts (18-45), helix angle 25°-45°, and height (0.33-0.55 mm). The fouling mechanism is a combination of precipitation fouling and particulate fouling and water hardness is 800 mg/L. Based on the Prandtle analogy, (Km/Kmp)/(f/fp) and (j/jp)/(f/fp)1/3 were used as evaluation indexes of heat transfer. Comparing to previous studies, this study is a comprehensive analysis involving the structure parameters of helical-rib tubes. A series of semi-theoretical fouling correlations as a function of the evaluation indexes were developed. The correlations can be directly used to assess the fouling potential of enhanced tubes in actual cooling water situations. ©2008 Chin. Soc. for Elec. Eng.