A Study of Practical Cooling Water-and Particulate Fouling Characteristics in Spiral-grooved Tubes

朱华,庄博,李蔚,钟昌雄
2008-01-01
Abstract:An experimental study has been performed of the fouling characteristics of a bare tube and of a group of 7 brass-made inbuilt spiral-grooved tubes with different thread heights, angles, and different numbers of thread and an inner diameter of 15.54 mm. Through a comparison and analysis of the test data of practical cooling water and particulate fouling, the main reasons for the difference existing between the bare tube and spiral-grooved one have been explained. The authors have concluded that the ratio of fouling thermal resistances of cooling water in the practical operation of a bare tube and spiral-grooved one will be linearly increased with an increase in the product of the area index and efficiency index. However, the linear function expressions in the two zones (p/e > 5.0 and p/e < 5.0) are different. The particulate fouling ratio assumes a linear ascending relationship with an increase of the efficiency index within only one zone during the experiment.
What problem does this paper attempt to address?