A New Protection Method of Metro Traction Electric Lines

Li Ziwei,Ning Lu,Wei Yuan,Jianrui Zhang,Xingjun Tian
DOI: https://doi.org/10.1088/1757-899X/631/4/042039
2019-11-07
IOP Conference Series: Materials Science and Engineering
Abstract:The recorded operational data shows that the DDL feeder protection malfunction is mostly caused by the unknown resonance in metro traction electric lines. To effectively solve the engineering problem restricting the operation safety of traction power supply, this paper proposes a new feeder protection algorithm based the feeder current waveform characteristics and the screening principle. The first step of algorithm is removing the working current from the great current by the traditional DDL protection algorithm, and the second step is eliminating the influence of the system resonant current. It is proved by lots of actual cases that the new combined algorithm not only has advantages of clear concept and simple pattern, but also can efficiently identify the short-circuit fault of the traction electric lines.
English Else
What problem does this paper attempt to address?