Field Modification and Application of ODAF Cooling System for 500kV Transformer

Huo Feng,Wu Jianling,Liu Shangbin,Yue Yonggang
DOI: https://doi.org/10.1088/1742-6596/1550/4/042024
2020-05-01
Journal of Physics: Conference Series
Abstract:Abstract A large number of oil flow relays and submersible pumps in the forced oil circulation mode of the main transformer have a huge workload of operation and maintenance. The main transformer of the ODAF cooling system has a large number of oil flow relays, and the submersible pump is prone to malfunction, which resulting in a large amount of maintenance work and the risk of the main transformer being forced to stop. Oil flow baffle and submersible pump running wear debris may affect the normal operation of transformer. This paper, through the field research and application of the transformation of the 500kV main transformer ODAF cooling system, carries out calculation of modification, analysis and calculation of cooling efficiency principle, etc.
What problem does this paper attempt to address?