Extinguishing High-Energy Fault Arc in Transformer Via Current Transfer with a Triggered SF6 Gap in Sub-millisecond

Zhibing Li,Xiaoang Li,Ran Zhang,Yikai Shao,Pan Jiang,Xiaodong Xu,Zhanfeng Zheng,Hao Cheng,Qiaogen Zhang
DOI: https://doi.org/10.1109/tpwrd.2024.3437732
IF: 4.825
2024-01-01
IEEE Transactions on Power Delivery
Abstract:This letter presented a novel method for fast extinguishing high-energy fault arcs (HFAs) in power transformer by transferring the current into a triggered gas gap. The verification test was conducted to prove its feasibility. Five shots of arc, with a length of 250 similar to 650 mm and a current amplitude of 20 similar to 50 kA, were ignited in a sealed oil tank to simulate the HFA in 550 kV transformer. A 120 mm high-pressure SF6 gap, with over 1.2 times of the insulation strength of 550 kV transformer, was triggered by an enhanced plasma injection (EPI) to bypass the HFA. In five shots of tests, HFAs were all been successfully extinguished within 1 ms once the SF6 gap was triggered. The results provided a novel and promising technique routine for quick removal of fault arc and thus risk control of resulting disaster of large oil-filled equipment, such as power transformers.