A Blocking Method for Bus Protection of CT Disconnection and Opening Method of HIF Based on Current Characteristics

Yudong Fang,Zhijie Wang,Zhenyang Chen,Yanjun Li,Chuan Feng,Jiawei Yuan,Zaibin Jiao
DOI: https://doi.org/10.1088/1742-6596/2731/1/012012
2024-01-01
Journal of Physics: Conference Series
Abstract:Abstract Current transformer (CT) disconnection in busbar can lead to erroneous operation of busbar differential protection. The existing methods for handling CT disconnection have not taken into account how to re-enable the protection in the case of high-impedance faults (HIFs). If the two types of faults cannot be distinguished in a timely manner, it can adversely affect the safe operation of the power grid. This paper provides a theoretical analysis of the differences between differential current and restraining current in the case of busbar CT disconnection faults and HIFs. Based on these characteristics, this paper proposes a criterion for CT disconnection fault blocking and a criterion for HIFs opening. Simulation results demonstrate that this method can effectively and accurately identify HIFs even in the presence of CT disconnection faults.