Polarity Comparison Fast Bus Protection for Asynchronous Sampling Fault Current

Yuanbo YE,Min XIE,Tongwen WANG,Yu WANG,Hanwen ZHANG,Zhiguo HAO
DOI: https://doi.org/10.3969/j.issn.1673-7598.2018.04.016
2018-01-01
Abstract:In order to overcome the problems resulted from data synchronization of distributed busbar protection and current transformer (CT)transient saturation,a novel fast busbar protection is proposed based on fault superimposed current polarity comparison.The bus protection takes the pre-fault voltage and pre-fault current as the new reference for polarity comparison,and utilizes the relationship between the pre-fault current and superimposed current to identify the fault direction. Theoretical analysis shows that when the bus fails,the current polarity of each line is same.When line faults,the component current polarity of fault line is opposite to that of other perfect circuits.The theoretical analysis and PSCAD/EMTDC simulation test show that the bus protection operates reliably and rapidly, its performance is immune to the saturation of the current transformer and the compatibility of the electronic transformer,and the protection reliability is high.
What problem does this paper attempt to address?