A CT Disconnection and High Impedance Fault Identification Scheme Based on Branch Zero Sequence Current Characteristics

Zhenyang Chen,Zhijie Wang,Yudong Fang,Yanjun Li,Chuan Feng,Jiawei Yuan,Zaibin Jiao
DOI: https://doi.org/10.1109/psgec62376.2024.10721118
2024-01-01
Abstract:High-resistance faults on the bus may be misjudged as current transformer (CT) disconnection faults by the protection system, leading to protection refusal and further development of the fault. Conversely, CT disconnection may be misjudged as a high-resistance bus fault, causing false tripping of the protection system. To accurately distinguish between these two faults, this paper uses a double bus double-section model to analyze the characteristics and differences of differential current, restraining current, and branch zero-sequence current under both fault conditions. Based on these differences, corresponding criteria are proposed and integrated into a complete identification scheme. Finally, PSCAD is used to simulate different fault scenarios to verify the accuracy of the identification scheme. The results show that this scheme can effectively identify asymmetric CT disconnection faults and high-resistance faults (HIF) on the bus.