Numerical Prediction Method for the Time History Response of Spot-Type Smoke Detectors to Fire Signals

Peng Pan
2009-01-01
Abstract:To predict the time history response of spot-type smoke detectors to fire signals,a parameter calibration method for the Cleary time lag model is proposed based on numerical wind tunnel experiments using the fire dynamics simulator(FDS) code.The JTY-GD-1109A light scattering smoke detector is used as the detection.Calibrated parameters of the detection's Cleary time lag model and the analytical results from the FDS fire simulations were combined to develop a model to predict the fire signal time history response in the sensing chamber,which is applicable to ceiling jets with velocities of 0.15-0.6 m/s.Predictions for a typical room fire agree well with the actual conditions in numerical tests.
What problem does this paper attempt to address?