Study Onthetransformer Protection Principle BasedonTheEquivalent Circuit Equation

Zhiguo Hao,Chu Yun-long
2005-01-01
Abstract:The mutualfluxcalculated fromtheequivalent circuit equation oftheprimary andsecondwingding isequal duringnormaloperation conditions, magnetizing inrush and external fault. Itdiffers duringaninternal wingding fault, groundfault andphasefault. A newtransformer protection algorithm basedon theequivalent circuit equation ofthe primary andsecondary winding mutualfluxisdescribed inthis paper. Forasingle-phase andathree-phase Y-Ytransformer, themutualfluxiscalculated. Fora transformer withdelta wingding, thedifferences ofthemutualfluxbetween thetwo phases arecalculated tousethelinecurrents. Because ofthe accuracy ofwinding parameter influencing thesensitiveness of protection algorithm, theleast square isadopted toidentify and correct theparameter value.Comparedtoa conventional harmonically restrained differential relay, thealgorithm is independent ofcorecharacteristics andsystemcondition. Test result indicates thatthealgorithm cansuccessfully discriminate between internal fault andallother operation conditions. IndexTerms-transformer protection, equivalent circuit equation, mutualflux, internal fault, inrush current