Study on anticorrosion of waste heat boiler economizer fin tube of gas turbine generator unit in standby state

YU Zhefeng,TAO Zhentao,XU Maoxian,YAN Fengping,ZHOU Yonggang,HUANG Yue,ZHAO Hong
DOI: https://doi.org/10.19666/j.rlfd.202301299
2023-01-01
Abstract:During frequent long-term standby state of gas turbine generator unit,the surface of 08A1 carbon steel of waste heat boiler economizer fin tube will have serious corrosion problems.In this paper,the macroscopic corrosion phenomenon and corrosion rate of 08A1 carbon steel above the critical humidity were studied by the method of hanging piece and electrical resistance probe.The results show that the corrosion rate of 08A1 carbon steel is the fastest in the first 5 days under the constant environment of 20 ℃ and relative humidity of 70%,and the corrosion depth reaches up to 0.85 μm,accounting for 47.7%of the total change in the whole process.However,the most obvious corrosion phenomenon,including the change of weight and the surface corrosion area,occurred from about the 19th to the 25th day.With the relative humidity gradually increasing from the critical humidity of 70%(ambient temperature 20 ℃),the corrosion evaluation indexes of 08A1 carbon steel show a linear upward trend.Nitrogen filling maintenance strategy under long-term standby state was formulated,effectively alleviating the corrosion condition of economizer fin tube of waste heat boiler.
What problem does this paper attempt to address?