Fault Analysis of DCSST MV Side Bipolar Short Circuit

Kaixin Zhang,Shenxing Shi,Xinzhou Dong
DOI: https://doi.org/10.1109/apap59666.2023.10348411
2023-01-01
Abstract:Based on DCSST equipment in the flexible medium voltage DC distribution network, this paper analyzes the fault of bipolar short circuit on the medium voltage side at the DCSST outlet from two aspects: control strategy and circuit structure. The dynamic response of control link is analyzed by Laplace transform, and the fault current characteristics in DCSST are analyzed by dynamic circuit method. The analysis shows that the low voltage side does not cause overcurrent due to fault, the fault current in the middle voltage side has two-stage characteristics, and the DCSST itself has the ability to block the fault current. Finally, the rationality and correctness of the analysis are preliminarily verified by PSCAD.
What problem does this paper attempt to address?