Improvement on Fault Time Accuracy of Power Sampling System

Donglai Zhang
2011-01-01
Abstract:With respect to the fault time accuracy of power system,the current researches focus on fault location algorithm based on sampled data.Considering the configuration of sampling frequency and specific implementation process of synchronous data in power sampling system,a new method was proposed for quantitative evaluation and improvement the accuracy of fault time through the establishment of phase error model of sampling system between the asynchronous sub-stations.In this method,the phase-shifts by the signal transmission were compensated using phase error mean at different frequency shifts,and before and after the fault time the sampling frequency was increased in short time by predicting fault based on the phase state estimation between the sampling systems in the asynchronous sub-stations.The measurement results shows that it is the approximate linear variation characteristics between the phase-shift and frequency-shift during the process of signal transmission,and system sampling frequency is limited by processing capacity of sampling system using the uniformly interval sampling.The proposed method is proved through the experiment and simulation,and it can provide an effective way to improve the fault time accuracy of power sampling system.
What problem does this paper attempt to address?