Retrofit of Air Preheater of 670 T/h Boiler in Xinhai Power Generation Company Ltd

Chuangxin Guo
2000-01-01
Abstract:Irrational design,serious partial abrasion of three dimensional sealing sheets and stationary seals,part of sealing sheets having lost their elasticity,high air leakage ratio(20%)etc.Problems existed in the 27VI(T) 1625 Ljungstrom tri sector regenerative air preheater made by Shanghai Boilers Works.For this reason,Haodunhua Engineering Co.Ltd retrofitted the sealing system.The main contents of retrofit include:a.The original sealing of air preheater were retrofitted to fixed sealing baffle system of Haodun;b.All the radial,axial sealing strips and inner,outer peripheral sealing strips were replaced,and all the sealing baffles were fixed.The measurements and testings after retrofit showed that,air leakage ratio was reduced to about 8%,and kept within 10% through 1.5 year of operation.The energy saving effect is remarkable.