Surge Protective Device Damage Caused by Triggered Lightning Return Stroke, Subsequent Continuous Current and M Component

Shaodong Chen,Xu Yan,Yijun Zhang,Weitao Lyu,Yang Zhang,Chang Chen,Lyuwen Chen,Yanfeng Fan,Sai Du
DOI: https://doi.org/10.2139/ssrn.4266671
2022-01-01
SSRN Electronic Journal
Abstract:In this study, the ground potential rise (GPR) resulting from the current injection into the ground grid triggered by lightning is observed. It is found that the GPR of the far-end ground grid counterattacks and damages a surge protective device (SPD) under the common ground connection of two ground grids. The charge accumulation reaches 2.27 C, and the energy accumulation impacting the SPD reaches 1,934.4 J, at which point the zinc oxide SPD (with a nominal discharge current of 40 kA) will fail. The analysis results show that the quantity of electric charge impacting the SPD is quite high in the process of superimposing multiple M components with large currents on continuous current following return stroke. The M component with high current is superimposed on the falling edge of the lightning return-stroke current waveform. The short time interval from the return stroke parent results in a high background current. Therefore, the electric charge quantity impacting the SPD is very high, and the damage effect and power are both significant.