Ground Potential Rise Between the Adjacent Ground Networks Based on One Artificially Triggered Lightning

颜旭,张义军,陈绍东,黄治钢,吕伟涛,陈绿文
DOI: https://doi.org/10.13336/j.1003-6520.hve.20170428033
2017-01-01
Abstract:In order to further study the voltage characteristic of the GPR when the close-range lightning stricks,we analyzed the data from artificially triggered lightning experiments of the elevated voltage of the GPR 40 metres apart.And the conclusion can be drawn that:(1) The peak values of GRPs related to 3 retum strokes ranges from-9.0 kV to-15.4 kV,then the GRPs fall to 51.1%,51.9%,and 53.9% of its peak value and forms 3 sub-peaks respectively within several microseconds.(2) The peak values of GPRs caused by M-component have a range of-0.3 kV to-3.0 kV,the average value is-1.0 kV;the scope of 10%~90% rising time is between 14.0 μs to 776.6 μs with a mean value of 190.7 μs,which is 1.5 times that in lightning current.(3)In the return stroke stage,the linear correlation coefficient of peak value and gradient between GPR voltages and direct lightning current are 0.96 and 0.98,respectively.The GPRs in return stroke stage is a combined effort of current discharge in soil and inductive coupling;In M-component process,the peak values of GPRs and direct lightning current are almost the same,however,the correlation coefficient of waveform gradient is just 0.73,which means the GPRs during M-component progress is mainly caused by lightning current discharge in soil,the inductive coupling can only be the secondary factor.The GPR between the adjacent grotmd networks will be long-time kept at a rather high level by M-component with the continuous current superposition,and that is an important reason for the damage of Surge Protective Devices (SPD) led by the ground potential counterattack between the adjacent ground networks.
What problem does this paper attempt to address?