Observation and Analysis of Lightning Current Distribution in the Common Ground Network Based on Triggered Lightning

Liang ZHU,Shaodong CHEN,Xu YAN,Yijun ZHANG,Weitao Lü,Lüwen CHEN
DOI: https://doi.org/10.13336/j.1003-6520.hve.20180211002
2018-01-01
Abstract:The analysis on characteristics of lightning current distributed in the common ground network is usually based on theory studies. Wer analyze the problem though field experiment and ATP-EMTP simulation,and have drawn the following conclusions. The average amplitude and quantity of the 5 return strokes in the flats which are used to connect the two independent ground networks are -1.2 kA and -0.24 C, respectively, and the ratios to lightning current are 7.8% and 27.0%, respectively. The average front time and the time of wave tail in the flat1 are 22.0 μs and 149.2 μs, which are 44 times and 16 times of the lightning,respectively. During a lightning process, the parameters of the M-component of which value is -19.3 kA in flat2 are similar to those of flat1s and are also similar to those of return stroke. According to the comparison of simulation and experiment, we find that the front time of return stroke agrees well with that of experiments when the wave tail is distinctly different in the flats. The simulation M-component agrees well with lightning current in the flats. The attenuation ratio between the lightning current and M-component caused by the network is larger compared to the return stroke, due to the transient effect of ground network the current distributed in the ground network and the ground potential rise (GPR) caused by M-component deserve more attention.
What problem does this paper attempt to address?