Abstract:As an important part of large-capacity converter transformer, on-load tap-changer gets a lot of attention in the aspect of reliability improvement technology. Existing pressure relief valve cannot work effectively after the failure of tap-changer, which will cause damage to the converter transformer body, fire and other faults. In this paper, a new pressure relief system is developed which combines pressure release valve and explosion-proof barrier board. Compared with existing products, the cumulative release flow in 60 ms of the proposed system is 2.6 times higher. It maximizes the release area with Y-type three-way interface, and reduces the internal pressure to half that with traditional pressure release valve. In addition, an explosion-proof isolation scheme is proposed to avoid on-load tap-changer faults affecting converter transformer body. The isolation arrangement reduces the maximum stress on oil tank to 35.9% that with original buried arrangement. Both simulation and experiments show that the proposed schemes are much better than existing products, which will effectively improve the reliability of on-load tap-changers.