Experimental Study on Discharge of Impurities in Oil of on Load Tap Changer of Converter Transformer

Jun Deng,Chen Liang,Zhicheng Xie,Zhicheng Pan,Jinyin Zhang,Haibin Zhou
DOI: https://doi.org/10.1109/ceepe55110.2022.9783436
2022-01-01
Abstract:Aiming at the problem of commutation failure caused by impurities contamination in the oil that occurred in the on-load tap-changer, a platform for the test of impurities in the oil of the on-load tap-changer was built, and the breakdown test of the impurities in the oil of the on-load tap-changer was proposed. Methods, the test obtained the breakdown characteristics of the on-load tap-changer in oil with uniform carbon particle contamination, local carbon particle contamination, rust contamination, and paint skin contamination, and revealed the breakdown process of the on-load tap-changer under local carbon particle contamination. The uniform carbon particle pollution, rust pollution and paint pollution will basically not cause the tap changer oil gap breakdown, carry out the core inspection of multiple on-load tap-changers, and found carbon pollution, rust pollution and paint pollution, Suggestions for improving the structure, installation process, operation and maintenance of the on-load tap-changer are put forward, which is an important reference for the structural improvement and failure cause analysis of the on-load tap-changer.
What problem does this paper attempt to address?