Abstract:Metal particles attached to the insulator surface will seriously distort the electric field along the surface, induce partial discharge and even cause flashover, which seriously threatens the normal operation of the equipment. The detection of partial discharge is one of the important means of insulation supervision. In this paper, the experimental platform of PD photoelectric joint diagnosis was built. The development characteristics of partial discharge of 126 kV basin-type insulator for GIS under AC voltage were studied. With the increase of the applied voltage, three stages were founded from the beginning of partial discharge to the approaching flashover. When the metal particles are located at different positions of the basin-type insulator, the change trend of the discharge amount with the voltage is the same, and both show a slow increase first and then an exponential increase trend.