Analysis on Effect of Protecting Transmission Lines from Shielding Failure by Sideward Rods Installed Onto Crossarm of Towers
沈志恒,赵斌财,周浩,邓旭,龚坚刚,姜文东,王灿灿,王武军,孙可,王东举
DOI: https://doi.org/10.13335/j.1000-3673.pst.2011.11.032
2011-01-01
Abstract:To assess the effect of protecting transmission lines from shielding failure by sideward rods installed onto crossarm of towers, a three-dimensional electrogeometrical model is proposed to calculate the protection range of sideward rod that protects transmission line from shielding failure, and the rule for its application and installation are summarized. Calculation results of typical transmission tower, which transmission lines in voltage classes from 110kV to 500kV are erected on, show that the sideward rod can effectively protect transmission lines, which are located in the dangerous area near the tower head, from shielding failure, thus the shielding failure trip-out rate can be decreased. Research results also show that the protective effect of sideward rod will be influenced by both rod length and installation position, so the length of the rod should be longer than two meters and have to be intalled onto the corssarm under larger angle of shade of overhead ground wire. Practical operational experiences show that the sideward rod can assuredly play an effective role in protecting transmission lines from shielding failure. Thus, it is an effective approach of protecting transmission line from shileding failure to install sideward rods onto the crossarms of transmission towers located in the regions with severe lightning damages such as mountain area and so on as well as onto the crossarms of tall transmission tower.