A comparative study on main influencing factors of outdoor sound field distribution of transformer chamber—A case study of 220 kV indoor substation

Luwen XU,Hui XIE,Fangfang LUO,Anxin ZOU
DOI: https://doi.org/10.11684/j.issn.1000-310X.2018.03.010
IF: 3.614
2018-01-01
Applied Acoustics
Abstract:In order to solve the problem of negative impact of indoor substation noise on the surroundings and investigate the outdoor noise distribution of the transformer chamber in the indoor substation,RAYNOISE software was used in this paper to simulate and analyze different types of doors,windows and inlets in 220 kV indoor substation, considering 1 main transformer in the transformer chamber. The simulation results have shown that the setting of acoustic doors has little effect on the outdoor sound field, but the effect of acoustic louver on the outdoor sound field is 3~4 dB higher than that of the normal louver. If both the door and louver are soundproofed, the noise reduction is 5~6 dB higher than the setting of normal door and louver. Through a series of simulations,this paper has developed the noise prediction models for the outdoor three-dimensional space of indoor substation, and scientific guidance and technical support have been provided for the noise control and retrofit engineering solutions of substation.
What problem does this paper attempt to address?