Noise Pollution Mitigation Method for Substations in Urban Communities Based on a Smart Silencing Unit

Donghui Wang,Liming Ying,Yongtian Jia,Lu Zhang,Fan Zhang,Wenyi Wang
DOI: https://doi.org/10.1016/j.jclepro.2019.118911
IF: 11.1
2020-01-01
Journal of Cleaner Production
Abstract:Minimizing the audible noise impact of a power system is one of the major measures for a cleaner power supply. In this study, a smart silencing unit was designed based on the universal design principles to mitigate the noise pollution of a substation. The corresponding large noise reduction coefficient (NRC), smart selective absorption characteristics at certain frequency bands, and a beneficial low-frequency sound absorption effect were verified through impedance tube and reverberation room tests. A comparison of the analysis results showed that after the installation of the smart silencing units, the average steady state maximal sound pressure level (SPL) acting on the surrounding community building surfaces decreased by 10.77 dB. Thus the substation audible noise impact of the substation on the ambient environment was properly limited. This innovative solution bridges the gaps between the acoustic absorption and insulation theory research field and the implementation of noise suppressing measures for an acoustic environment friendly substation. Consequently, a cleaner power supply and soundscape compatibility between the substation and surrounding communities can be achieved more readily. (C) 2019 Elsevier Ltd. All rights reserved.
What problem does this paper attempt to address?