Applying Virtual Sound Barrier At A Room Opening For Transformer Noise Control

Jiancheng Tao,Suping Wang,Xiaojun Qiu
2015-01-01
Abstract:A virtual sound barrier is applied for active control of noise from 180 MVA transformers in an enclosure. The system consists of 15 loudspeakers, 15 error microphones and a multi channel adaptive feedforward active control controller. The loudspeakers are placed with 45-75 cm intervals at a 5.4 square meters opening of the enclosure, the microphones are 1 m away in front of the loudspeakers facing noise radiation directions, and the multi channel controller adopts a specific transformer noise control algorithm with an internally synthesized reference signal. Measurement results show that the average noise reduction at the error microphones is 12.7 dB for 100 Hz, 19.9 dB for 200 Hz and 22.2 dB for 300 Hz, and the noise reduction still remains 5.4 dB for 300 Hz in the far field points 7 m away, which can match the noise reduction performance of the closed window onsite. The advantages of the proposed system are natural ventilation and lighting, effective saving in space, and easy maintenance for the transformers.
What problem does this paper attempt to address?