Steady-State Thermal Performance of Radiant Wall Embedded with Capillary-Tubes

Siyu QIN,Yuang WANG,Yang LI,Song GAO,Min ZHAO,Zhao LU,Qiongxiang KONG,Liwen JIN
DOI: https://doi.org/10.7652/xjtuxb201805020
2018-01-01
Abstract:To explore the performance of the wall embedded with capillary-tubes,a scale model of heat distribution of the capillary wall is established,which delivers the ratio of heat exchange from capillary layer to both indoor and outdoor sides according to the simplified transient RC (resistance and capacity) model.The experimental data including the indoor and outdoor air temperatures,the temperature of the inner surface of the capillary wall,the temperature of the capillary layer and the heat fluxes from capillary layer to indoor and outdoor sides are collected to analyze the characteristics of the capillary wall and the heat exchange crossing indoor and outdoor sides subject to the winter conditions.The reasonability of the present scale model is verified,and the one-dimensional heat exchange process of the capillary wall is then discussed.Experimental results show that the capillary radiant air-conditioning system is endowed with good stability,and the fluctuation of the indoor temperature is relatively small.With the increase in the running time of the system,the calculated values of the model are more consistent with the measured results.The proposed model is capable to handily evaluate the performance of the capillary wall in actual applications and to provide a theoretical basis for the further research on indoor load calculation of the radiant air conditioning system.
What problem does this paper attempt to address?