Experimental study on wall and ceiling capillary radiant cooling performance

Chenqiu DU,Baizhan Li,Hong Liu,Yong Cheng,Jinhua Chen
2018-01-01
Abstract:Analyses the indoor thermal environment responses and comfort of wall and ceiling capillary radiant cooling at the system water supply temperatures of 16 ℃ and 18 ℃,respectively.The results show that the indoor thermal environments of both terminals can be stabilized within 4 hours and both the temperatures in steady-state are kept at 28 ℃.The difference of heat flow per unit area of wall radiant cooling is up to 20.62 W/m2 for the capillary tube distances of 2 cm and 4 cm.The indoor vertical and horizontal temperature distribution of both terminals are uniform,and the thermal environments of wall and ceiling radiant cooling systems are evaluated as Grade Ⅱ (0.5<PMV≤1) and Grade Ⅰ (PMV≤0.5) in steady-state,respectively.The indoor thermal environments of two radiant terminals can meet the comfort requirements of the standard.