Study on Infiltration Through Doorway of Cold Store based on Unsteady RANS Model

Shen Tian,Shuangquan Shao,Kunzhu Zhang,Changqing Tian
DOI: https://doi.org/10.3969/j.issn.0253-4339.2017.03.063
2017-01-01
Abstract:Because the total gross of cold stores is increasing, the energy consumption of cold stores is attracting increasing attention. In-filtration through the doorway, which accounts for a large part of the total heat load, has become an important research focus with regard to the energy consumption of the cold store. In this paper, by using an unsteady RANS model, a transient infiltration simulation model is es-tablished. By utilizing a cold store with height ratio between the cold store and the door 2:1, experimentally measured data under condi-tions with different temperature differences and operation modes of the cooling fans are used to validate the model. The results show that the predicted value and change trends of the infiltration air volume, local wind speed, and temperature of the established model agree well with the experimental data. The predicted error for the infiltration air volume before 40 s of door-open time is ± 10%. By using this mod-el, the characteristics and mechanism of the infiltration are analyzed. The results show that, owing to the effect of the airflow made by cooling fans, the temperature in the cold store when the fans are on is lower than that when the fans are off. There is little density differ-ence between the warm air and the cold air. The gravity imposed on the cold air has little variation. Thus, the infiltration air volume chan-ges linearly with the door-open time.
What problem does this paper attempt to address?