Traveling wave fault location measurement method based on LMD

Weixin LIU,Songbin ZHOU,Yisen LIU,Wei HAN,Hongzhao ZHANG
DOI: https://doi.org/10.11857/j.issn.1674-5124.2017.09.008
2017-01-01
Abstract:In view of the problem of the wave velocity uncertainty and the inaccurate measurement of the arrival time of initial traveling wave in travelling wave fault location measurement of transmission line, a traveling wave fault location measurement method based on local mean decomposition (LMD) is proposed in this paper. It can eliminate the influence of wave velocity to fault location measurement by adding a measurement point in the middle of the traditional Double-Ended Traveling Wave and calculating the traveling wave velocity with the length of fault-free line segment and the time that the initial wave is tested at the measurement point. The local mean decomposition is applied to decompose the line mode component of measured current wave, and the arrival time of the initial traveling wave can be detected according to the first sudden arising of frequency in the instantaneous curve of the first PF obtained through LMD. The transmission line simulation model of the Simulink is established in the paper. The results of the simulation comparison conducted for LMD, Wavelet Transform and Hilbert-Huang Transform (HHT) show that LMD has higher fault location measurement accuracy than the schemes based on either wavelet transform or Hilbert-Huang transform and it has a certain reference value to transmission line fault location measurement in practice.
What problem does this paper attempt to address?