Research on extraction of characteristic energy of radiated E-field method in evaluating GIS status

Jinpeng Hao,Hongye Zhang,Fei Guo,Jun Guo,Xiuguang Li,Xutao Wu
DOI: https://doi.org/10.3969/j.issn.1001-1390.2018.03.022
2018-01-01
Abstract:Switching operations of a disconnecting switch (DS) or a circuit breaker (CB) in a gas insulated substation (GIS) can stimulate outside GIS strong radiated electromagnetic fields.In order to assess the health status of GIS through its measured characteristic parameters,a method of extracting the characteristic frequency-band energy of the electric field (E-field) based on wavelet packet analysis is proposed.The radiated E-field signals of CB in good condition and those of CB in which insulation fault happens are separately decomposed into 4 layers by using the bior5.5 wavelet basis function,and the normalized energies of different frequency bands are extracted;then,it's found that the frequency band below 31.25 MHz is the characteristic frequency band of radiated E-field.By comparing the energies in the characteristic frequency bands after a random CB operation with that of the typical radiated E-field obtained when GIS totally is in good condition,insulation faults of CB can be detected and the operating state of GIS could be evaluated.
What problem does this paper attempt to address?