Experimental Investigation into the Flow Coefficient of a Quick-open Ball Thermal Expansion Valve

Xu-Ming XIE,Chang-qing TIAN,Wen-xing SHI
DOI: https://doi.org/10.3969/j.issn.1005-0329.2005.05.001
2005-01-01
Abstract:The law of flow coefficient affected by valve lift, refrigerant inlet density and refrigerant outlet steam quality was investigated based on quick-open ball thermal expansion valve. It was indicated that the flow coefficient doesn't nearly affected by valve lift, but mainly affected by refrigerant inlet density and refrigerant outlet steam quality after analyzed a great deal of experiment data. Adopting a Nonlinear Least-square Technique, obtains the flow coefficient correlation of quick-open ball thermal expansion valve.Experiment results showed that the maximum relative error between the refrigerant flow calculated by the fitting correlation and the true flow is ±5%.
What problem does this paper attempt to address?