Investigation on the Effect of the Internal Heat Exchanger on System Performance of Trans-critical CO2 Heat Pump

Dong-zhe LI,Xiang YIN,Yu-long SONG,Feng CAO
DOI: https://doi.org/10.3969/j.issn.1006-2971.2016.04.002
2016-01-01
Abstract:In order to investigate the effect of the internal heat exchanger, the model of the trans-critical CO 2 heat pump system was established in Dymola. Based on the Modelica language, the COP and the heating capacity of the system with and without internal heat exchanger (IHX) were investigated, besides the pressure of evaporation, CO2 outlet temperature of gas cooler, and degree of su-perheat, etc. It was found that the operation performance and operation stability of the system with IHX were better than the one without IHX. Under specific condition, COP and optimum discharge pressure of the system with the IHX was 1.6% higher and 5%lower than that of the system excluding the IHX, respectively. Meanwhile, the pressure in the evaporator with IHX fell down, decreas-ing the mass flowrate, and the temperature difference between CO2 outlet and water inlet of gas cooler was smaller due to the suffi-cient heat transfer. Additionally, there was superheating in the system with IHX. The degree of superheat had direct effect on the heat pump system as it could rise the enthalpy and discharge temperature of compressor outlet, thus increasing the heating capacity. Therefore, it was useful to realize the operation point parameters in detail and provide the reference for the whole system and each component of trans-critical CO2 heat pump system by investigation on the IHX.
What problem does this paper attempt to address?