Performance Analysis of Internal Heat Exchanger‐Based Quasi‐Two‐Stage Vapor Compression Heat Pump System for High‐Temperature Steam Production

Zhang Hao,Zhang Yanting,Xu Jingyu,Wang Lin,Huang Zheng
DOI: https://doi.org/10.1002/ente.202000623
IF: 4.149
2020-10-28
Energy Technology
Abstract:<p>The thermodynamic performance of a High‐Temperature Heat Pump Steam (HTHPS) system is determined mainly by its different cycle configurations. The present study involved improving the thermodynamic performance of a quasi‐two‐stage vapor compression high‐temperature heat pump based on a front internal heat exchanger (IHX) and rear internal heat exchanger cycle, and analyzing the influence of an internal heat exchanger. The present study established thermodynamic models for Front Reheating Structure (FRS) and Rear Reheating Structure (RRS) models on the basis of conservation of mass and energy. The system was compared to the traditional TF quasi‐two‐stage compression cycle system in terms of thermodynamic parameters. The results demonstrated that the thermodynamic performance of RRS was optimized under the same conditions. The RRS system exhibited an increase of 4.87% in the COP when the exhaust superheats is maintained are under 5K. Moreover, with an increase in the condensation temperature, the required mass flow of the refrigerant in the traditional system was 9.94%–12.36% higher compared to the RRS system, the power consumption of the compressor was increased by 3.9%–5.6%, and the steam output per unit refrigerant was decreased by 1.04%–5.07%. Furthermore, the Aspen Plus simulation verified that the reason for the change in the exhaust superheats was the different pressure ratios in the theoretical calculation, which is more practical.</p><p>This article is protected by copyright. All rights reserved.</p>
energy & fuels
What problem does this paper attempt to address?
The paper attempts to address the issue of improving the thermodynamic performance of high-temperature heat pump steam systems (HTHPS). Specifically, the paper studies the performance of a quasi-two-stage compression high-temperature heat pump system based on pre- and post-internal heat exchanger (IHX) cycles and analyzes the impact of IHX on system performance. ### Main Issues 1. **Improving the thermodynamic performance of high-temperature heat pump systems**: - High-temperature heat pump systems face issues such as high pressure, high exhaust temperature, and low heating coefficient when producing high-temperature hot water and steam. - The quasi-two-stage compression system reduces the compressor's exhaust temperature and improves the heat transfer rate by dividing the first-stage compression process into two sub-stages (quasi-first-stage compression and quasi-second-stage compression). 2. **Optimizing the impact of IHX position on system performance**: - The study compares two different IHX position systems, the front reheating structure (FRS) and the rear reheating structure (RRS), and analyzes their thermodynamic parameter changes at different condensation temperatures. - By establishing a thermodynamic model, the unit COP, compressor exhaust temperature, and steam output of the FRS and RRS systems are evaluated. ### Specific Objectives - **Evaluating the impact of IHX on system performance**: - Through simulation and experimental data, verify the impact of IHX at different positions on system performance. - Analyze the performance of IHX at different condensation temperatures to determine the optimal IHX position. - **Optimizing the thermodynamic performance of high-temperature heat pump steam systems**: - Compare the performance differences between traditional quasi-two-stage compression systems and FRS and RRS systems. - Propose improvement measures to enhance the system's COP and steam output. ### Conclusions - **Performance advantages of the RRS system**: - Under the same conditions, the COP of the RRS system is 4.87% higher than that of the traditional system. - As the condensation temperature increases, the refrigerant mass flow rate of the traditional system is 9.94% to 12.36% higher than that of the RRS system, the compressor power consumption increases by 3.9% to 5.6%, and the steam output per unit refrigerant decreases by 1.04% to 5.07%. - **Optimal position of IHX**: - The post-IHX can better optimize the thermodynamic performance of the system, increase the heat absorption of the refrigerant in the evaporator, and reduce the energy consumption of the compressor without changing the gas replenishment of the flash tank. Through these studies, the paper provides theoretical basis and technical support for the optimized design of high-temperature heat pump steam systems.