Typical Characteristics of Ferroresonance in Dispatching Center

SHI Wenjiang,LI Chunping,WANG Rui,LI Run
DOI: https://doi.org/10.7500/AEPS20140504011
2015-01-01
Abstract:The typical characteristics of ferroresonance accident happening in a network grounded with arc extinguishing coil are manifested in multiple times by 3U0 off-limit alarm,with two of the three-phase voltage and its historical curve,protection alarm,arc extinguishing alarm information appearing in pairs in the dispatching automation interface.They can be used as the ferroresonance comprehensive criterion,while ferroresonance recognition time is no longer than 10 minutes by the standard identifying process.
What problem does this paper attempt to address?