Novel Fault Components Extraction Approach for Double-circuit Transmission Lines on One Pole

Zhen-feng LIANG,Xiao-ning KANG,Jia-le SUONAN
DOI: https://doi.org/10.3321/j.issn:1000-1026.2005.20.010
2005-01-01
Abstract:Traditional fault component extraction approach can only satisfy the practical requirement in 2 or 3 cycles after fault inception Based on the result of phase selection, a novel approach of fault component extraction is proposed for double-circuit transmission lines on one pole. The double-circuit transmission line is decomposed into the same directional component mode network and the circumfluent component mode network. The analysis demonstrates that the positive and negative sequence current distribution coefficients in the same directional component mode network coincide with that in the circumfluencc component mode network. The proposed method can extract fault components correctly during the whole fault process and is free of influences of load and network parameters, etc. The digital simulation verifies the validity of the technique.
What problem does this paper attempt to address?