Steady-state Modeling of Controllable Shunt Reactor of Transformer Type

Xianbo KE,Xiaoqiang SUN,Lin CHENG,Jun LIU
DOI: https://doi.org/10.3969/j.issn.1673-7598.2018.03.004
2018-01-01
Abstract:The paper discusses the working principle of controllable shunt reactor of transformer type (CSRT) in detail,analyzes the relationship between low voltage controllable windings,and establishes the steady state mathematical model of the equivalent impedance of the CSRT,which contains only easily available transformer leakage reactance parameters.According to the proposed mathematical model,the paper calculates the equivalent reactance of the CSRT with quantitative relationship to firing angle and the number of switched windings,verifying the characteristic of the CSRT that its reactance can be adjusted continuously.In addition,from the viewpoint of engineering application of the CSRT in actual ultra-high voltage power grid,the paper analyzes high operation voltage problem under light load condition induced by the operation of security and stability control device after some special faults,and investigates the influence of the CSRT on the system bus voltage level and the transmission power of some key transmission sections.
What problem does this paper attempt to address?