Synthesis Load Model with Ideal Transformer

JU Ping,TANG Yong,SHEN Weiwei,FANG Shengwen,CHEN Qian
DOI: https://doi.org/10.3969/j.issn.1006-6047.2011.08.001
2011-01-01
Abstract:The SLM(Synthesis Load Model) is being promoted,which represents the distribution network and the reactive power compensation more accurately.However,it does not consider the role of transformer in distribution network,which may lead to much lower low-voltage bus voltage in some cases,resulting in improper system calculation.A SLM-T(Synthesis Load Model with Transformer) is proposed by adding an ideal transformer to the SLM,which cooperates with the reactive compensator to stabilize low-voltage bus voltage.Its parameter identification method is developed and the corresponding steps are presented.The effects of SLM,SLM-T with inconstant transformation ratio and SLM-T with fixed transformation ratio are analyzed by case simulation for different distribution network reactances.SLM-T with inconstant transformation ratio is recommended.