INFLUENCE OF HARMONICS ON REGESTRATION OF VARHOUR METER

XU Yi-xun,CHENG Hao-zhong,GE Nai-Cheng,ZHANG Wei-zheng
DOI: https://doi.org/10.3321/j.issn:1000-3673.2005.16.012
2005-01-01
Abstract:At present the research of the influence of harmonics on registration of varhour meter is still imperfect. The authors analyzed the phase-shifting errors of common used varhour meters, then the experiments of frequency response and reactive power of harmonics are carried out, and the results of experiments are analyzed by least square method. The results from theoretical and experimental analysis show that in harmonic environment the metering errors of varhour meter can be divided into amplitude error and phase error. Meanwhile there are evident phase errors in both induction varhour meter and solid-state varhour meter, so the maximum metering error may be twice as much the apparent power of harmonics. With the increment of harmonic order, the amplitudes of reactive harmonic power metered by induction varhour meter and solid state varhour meter are decreased and the metered amplitude by induction varhour meter decreases more rapidly.
What problem does this paper attempt to address?