INFLUENCE OF HARMONIC CURRENT ON METERING ERROR OFINDUCTION PHASE WATT-HOUR METERS

徐柏榆,邓志,梅桂华,刘春权,张新建
DOI: https://doi.org/10.3321/j.issn:1000-3673.2002.09.009
2002-01-01
Abstract:The influence of harmonics on induction watt-hour meter is expressed as the superposition of harmonic energy and harmonic current respectively, because the cause of metering error by harmonic current is rather complicated, so it is hard to estimate. In this paper the metering error caused by harmonic current is divided into three parts, i.e., the compensation error which is due to the dividing flux plate, the additional torque error which is due to the additional harmonic power led by the joint action of equivalent additional harmonic voltage caused by the saturation of voltage coil and the harmonic current with same order in the power line and thirdly waveform error. The first two errors are analyzed quantitatively and qualitatively, for the third error merely the influence of the interruption of current waveform on the error is analyzed and the measured results of this kind of error are given. The results of analyses and measurements show that the metering error is mainly consisted of the first two errors and the third kind of error can be neglected. In the measured results it can be seen that in high voltage power networks because the harmonic current is not notable so its influence can be not considered, however, in low voltage distribution networks the harmonic currents, especially the third order of harmonic current, is remarkable, therefore, sometimes the metering error caused by harmonic currents can not be neglected.
What problem does this paper attempt to address?