Effect of Electric System Disturbances on Torsional Vibration of Turbine Generator Shaft Systems and Active Control of Torsional Vibration

GAO Wen-zhi,LIU Jian-guo,HAO Zhi-yon
DOI: https://doi.org/10.3969/j.issn.1674-7607.2005.02.004
2005-01-01
Abstract:In this paper, a new idea of active control for torsional vibration that is global optimum control of linear constant quadratic form is applied in attenuate torsional vibration caused by electric system's disturbances. Electric system faults (such as 3-phase short circuits, 2-phase short circuits) are described, and the effect of faults on the maximum electric-magnetic torque is discussed. The impulse torque and response of torsional vibration of turbo-generator shafts are computed, and a simulation calculation on the basis of the global optimum control theory of linear constant quadratic form is conducted. The results of simulation show that active, control is very effective in attenuating torsional vibration of large turbo-generator shafts caused by disturbances.Figs 7 and refs 8.
What problem does this paper attempt to address?