Insulation Design for a 1.2 MV Enclosed Marx Generator

Rui LIU,Naigong ZENG,Xinxin Wang
DOI: https://doi.org/10.3969/j.issn.1003-6520.2005.04.026
2005-01-01
Abstract:In order to ensure the safe operation of a 1.2 MV Marx generator in a grounded metallic tank of limited volume filled with pressurized SF 6 gas or transformer oil, 3-D electric field in the tank is calculated using Ansoft software. The results show that the highest electric field always appears at the sharp corner of the metallic shell of the last stage capacitor and is higher than the breakdown field of the pressurized SF 6 gas or transformer oil. After rounding the sharp corner by mounting a metallic hemisphere on the capacitor shell, the highest electric field is much reduced to a value that is lower than the breakdown field of the pressurized SF 6 gas or transformer oil. In the end, transformer oil is chosen as insulation in the tank.