Surface Charge Accumulation Characteristics of Converter Transformer Valve-side Bushing and Influence on DC Transient Electric Field
Shifeng Shi,Qingyu Wang,Haitao Yang,Wei Yang,Gengsheng Xie,Yang Li,Guangzhong Yang,Zongren Peng
DOI: https://doi.org/10.1109/tdei.2024.3496841
IF: 2.509
2024-01-01
IEEE Transactions on Dielectrics and Electrical Insulation
Abstract:Under long-term exposure to high DC voltage, the converter transformer valve-side bushing will accumulate surface charge at the solid insulation interface, which affects the distribution of electric field inside the bushing, and even triggers the bushing insulation failure. To address the problem of surface charge accumulation in converter transformer bushing, this paper builds a bushing core surface potential measurement system, proposes a bushing DC field model considering weak gas ionization and surface conductivity, and carries out experimental measurements and simulation analyses on the surface potential distribution characteristics of the bushing core. Meanwhile, the transient change process of the bushing electric field under DC withstand voltage is simulated and calculated for the actual ultra-high voltage (UHV) converter transformer valve-side bushing structure. The results show that the surface potential distribution of the bushing core has a nonlinear relationship with the applied voltage, and there is a polarity effect, while the surface current is the dominant factor for the surface charge accumulation. The research results of this paper can provide a theoretical basis for the insulation structure design of converter transformer valve-side bushing, and play an important supporting role in improving the reliability of bushing insulation.